|
When
do I use a Terminating Resistor while communicating
over an RS485 Bus?
Termination
is used to match impedance of a node to
the impedance of the transmission line being
used. When impedance is mismatched, the
transmitted signal is not completely absorbed
by the load and a portion is reflected back
into the transmission line. If the source,
transmission line and load impedance are
equal these reflections are eliminated.
There are disadvantages of termination as
well. Termination increases load on the
drivers, increases installation complexity,
changes biasing requirements and makes system
modification more difficult.
The decision whether or not to use termination
should be based on the cable length and
data rate used by the system. A good rule
of thumb is if the propagation delay of
the data line is much less than one bit
width, termination is not needed. This rule
makes the assumption that reflections will
damp out in several trips up and down the
data line. Since the receiving UART will
sample the data in the middle of the bit,
it is important that the signal level be
solid at that point. For example, in a system
with 2000 feet of data line the propagation
delay can be calculated by multiplying the
cable length by the propagation velocity
of the cable. This value, typically 66 to
75% of the speed of light (c), is specified
by the cable manufacturer.
For our example, a round trip covers 4000
feet of cable. Using a propagation velocity
of 0.66 × c, one round trip is completed
in approximately 6.2 µs. If we assume
the reflections will damp out in three “round
trips” up and down the cable length,
the signal will stabilize 18.6 µs
after the leading edge of a bit. At 9600
baud one bit is 104 µs wide. Since
the reflections are damped out much before
the center of the bit, termination is not
required.
There are several methods of terminating
data lines. The method recommended by Electro
Industries is parallel termination. A resistor
is added in parallel with the receiver’s
“A” and “B” lines
in order to match the data line characteristic
impedance specified by the cable manufacturer
(120 ohms. is a common value). This value
describes the intrinsic impedance of the
transmission line and is not a function
of the line length. A terminating resistor
of less than 90 ohms should not be used.
Termination resistors should be placed only
at the extreme ends of the data line, and
no more than two terminations should be
placed in any system that does not use repeaters.
This type of termination clearly adds heavy
DC loading to a system and may overload
port powered RS232 to RS485 converters.
Another type of termination, AC coupled
termination, adds a small capacitor in series
with the termination resistor to eliminate
the DC loading effect. Although this method
eliminates DC loading, capacitor selection
is highly dependent on the system properties.
System designers interested in AC termination
are encouraged to read National Semiconductors
Application Note 903 located at http://www.national.com/an/AN/AN-903.pdf
for further information.
I
am using another Manufacturer's RS232 to
RS485 converter and I cannot get it to communicate
with the Nexus® meter. What is the problem?
.
Before
we answer this question, let me explain
about the two types of converters that are
typically used. The first is your basic
interface only converter, and the second
is a converter that supports Send Data Control.
What determines the type of converter that
is used is the software that is being used
with the converter and the cost.
Basic
Converters
The basic interface only converter needs
RTS Control. RTS Control is relevant only
if you are converting to 2-wire RS485 (where
the converter is a Master or a Slave) or
to 4-wire RS485 (where the converter is
a Slave). RTS Control is a method with which
the RS232 device (typically a PC) tells
an RS232-RS485 converter when it should
enable its RS485 driver, i.e. when it should
be transmitting. On a converter, which is
an interface converter only and does not
monitor the data, an external signal is
required. When providing RTS Control, the
RS232 device raises its RTS output immediately
before it starts to communicate, and drops
it after the last stop bit of the message
has been transmitted. The converter uses
this signal to control its RS485 driver.
The advantages of using RTS Control is that
the converter is simpler and therefore cheaper,
and it does not care about the baud rate
(within its limits) or the number of bits,
parity, etc. If this was the case with software,
or with an RTU, there would be more set
up decisions on the software in order to
communicate with a meter increasing the
software’s difficulty and decreasing
speed due to longer delay times. This is
not the best solution and often is the cause
of the problems in the field. It is better
to have a converter that automatically controls
the RTS signal, thus eliminating software
and RTU additional requirements.
The
following diagram illustrates a message
comprising of two characters and the RTS
Control signal, which would be required
to successfully transmit this message. Both
characters are shown as 8-bit data (or 7
bits with parity).

When
using Communicator EXT or any other Electro
Industries software the converter that supports
automatic Send Data Control should be used.
Converters
with Automatic RTS Control
A more sophisticated converter, e.g. the
Electro Industries Unicom 2500, does not
need RTS Control from the RS232 portion
because it generates the control signal
internally by monitoring the data with a
microprocessor. The Baud rate, and the DCE
and DTE switch is all that is required to
set on the Unicom 2500 converter. The converter
does the rest. This is considered the superior
because it is significantly easier to configure
and is not dependent on the configuration
of the software and the RTU. Electro Industries
recommends this solution exclusively, not
just to our devices, but for ALL RS485 speaking
devices. Better converters provide better
capability, easier use and more reliability.
The
Electro Industries Unicom 2500 is an industrial
converter that uses automatic Send Data
Control. it is also available with an optional
Fiber option. This converter, additionally,
is optically isolated to 2500 volts to protect
the remote devices from destructive electrical
anomalies. For more information, the brochure
is located at: http://www.electroind.com/pdf/Unicom2500_118702.pdf
or for the manual http://www.electroind.com/pdf/unicomman.pdf.
What
is the sample rate of the High Speed (HS)
inputs?
The Nexus® 1250 meter will sample the
HS inputs at up to 2 independent rates,
depending upon the configuration of the
unit. The HS inputs can be used for either
pulse accumulation or for status change
to record a waveform. The HS inputs are
always sampled at 100 times per second,
and debounced for 2 sample times. Your pulse
rate needs to be within its tolerance. If
the Nexus® meter has been ordered with
the optional 2 meg or 4 meg memory and the
user has selected the HS input to be used
for waveform recording, the HS inputs are
sampled at a rate that is based upon the
user selected waveform sample rate which
is much faster than the pulse counting rate.
The unit will record the waveform instantaneously
based on the change of a status input.
How can I communicate
with the Nexus® 1250 Meter?
The Nexus® 1250 meter has four communication
ports, three are designed to use the RS485
interface, and one is bidirectional between
RS485, and RS232. For direct connections,
it is easy to use the RS232 port, and a
standard serial extension cable (straight),
or using an RS485 to RS232 converter, such
as our Unicom 2500, connect to any of the
RS485 ports. The Nexus® 1250 Meter can
be remotely located, and using an external
or the optional internal modem, be accessed
across the PSTN with standard dial-up modems.
The meter can also talk across a LAN or
the Internet using the internal TCP/IP network
interface. Additional interfaces include
Modbus RTU, Modbus ASCII and DNP 3.0.
What is the response
time (RTU function) from condition change
to status output change?
Response
time is typically less than 200 mSec. per
Output Module, and can be extended to many
seconds by programming additional delay
times, associated with individual outputs.
Many factors may also influence this response
time. The number of Output Modules connected
to the Nexus® meter (each will be polled
in turn, and time between polls depends
on the module type and the amount of information
that must be retrieved or set), the baud
rate of the communications between the Nexus®
meter and the Output Module.
What
is the VAUX input used for?
This is an independent voltage input that
has all the capabilities of the other voltage
inputs (recording, triggering, trending,
etc.). A typical use would be in synchronizing
a line closure. With the Nexus® meter
connected to one side of a breaker, the
VAUX can be connected to the other side
of the breaker, and using the real time
phasor display of the meter, watch the VAUX
phasor relationship to the other inputs.
Another application would be to use the
Aux voltage to provide you the potential
from neutral to ground. This enables a user
to test the grounding system of a substation
or facility.
Can
I change the relay modules connected to
the Nexus® meter and manually change
the state of them through the Modbus registers?

How
does the DNP Level 2 dead band percentage
work in my Nexus® 1252/62/72 meter?
Understanding
Deadband %
In
the Communicator EXT software, the users
can customize the DNP object map. From Analog
Input data (Object 30), Analog Event data
(Object 32) can be created by its Deadband
percentage. Deadband percentage values set
the limit for event data. This Deadband
percentage value can be calculated from
the Full Scale value. The following example
will explain the usage of Deadband percentage.
Example:
The Nexus® 1252 meter has the following
setup in the programmable settings.
<Figure
1. Full Scale Values>
Device
Profile: Limit and Waveform Full Scales
I
A, B, C, Nc: 800.00
I Nm: 800.00
V AN, BN, CN: 6351.00
V AB, BC, CA: 11.00k
V Aux: 6810.00
Power Phase: 9600.00k
Power Total: 28.80M
Frequency: 50.00 |
Example
for Current
From the figure 3, the Deadband percentage
is 1.00 % for all readings. The range of
Deadband percentages are from 0.01 % to
326.67 %. For the IA, IB, IC, the full scale
is 800.00. The 1 % of 800.00 is 8.00. Analog
input data is scanned after 5 second of
meter power up. After that, new Analog input
data is scanned every second or faster (For
tenth second readings). If the value changes
by this Deadband percentage, the event data
will be created. For example, IA is 200.00
A after 5 seconds of meter power up. After
that, newly scanned IA reading will be compared
with 200.00 A. If a new IA reading becomes
208.00(1%) or higher, the event data will
be created. After that, the new IA readings
will be compared with 208.00 A. This is
the same for the opposite direction. If
the reading becomes 192.00A or lower, the
event data will be created. After that,
new IA readings will be compared with 192.00
A.
Internally,
the meter measures the readings in secondary.
From the figure 2, the IA has the ratio
of 800.00:5.00. This means that the Nexus
meter reads 1.25A secondary for 200.00 A
Primary. It is 0.05 A change for 1 % Deadband
internally. All computations are scaled
down by CT and PT ratios.
Example
for Voltage
This reasoning is the same for the Voltage
readings. For the VAN, VBN, VCN, the full
scale is 6351.00. The 1 % Deadband is a
change of 63.51. If the voltage reading
changes by 63.51 V, the event data will
be created. The ratio for voltage is 7200.00:72.00.
That means that 1% Deadband is a change
of 0.6351 V internally.
Example
for Power per phase
Power Phase has 9600.00 k full scale. 1%
Deadband is a change of 96.00k. Therefore,
if the power readings (Watt, VAR, VA) change
by 96.00 k, the event data will be created.
The power phase ratio is 16,000:1 from CT,
PT ratios (160:1, 100:1). Internally, 1%
Deadband is 6. 1 % Deadband is tight for
power readings. The event data will be created
by small changes of phase angles between
voltages and currents also.
Example
for Power total
The Power total has 28.80 M for full scale.
1 % Deadband is 0.288 M. Therefore, the
event data will be created if Power total
changes by 288 k (Watt, VAR, VA). The ratio
for Power Total is also 16,000:1. Internally
1 % Deadband is 18.
<Figure
2. CT and PT ratio>
Device
Profile: CT and PT Ratios
I
A, B, C: 800.00: 5.0
I Nm: 800.00: 5.00
V A, B, C: 7200.00:
72.00
V Aux: 7200.00:
72.00
Hookup: Wye
Operational Frequency
Range: 20Hz to 65Hz |
< Figure 3. DNP Customized Map>
How
do I get the GE SC-6 (USB to Optical Converter)
to communicate to my Nexus™ Socket
Meters?
1 |
|
Remove
the lens film before use. |
|
|
|
2 |
|
Plug
the device in.
:XP, NT: Should auto detect the
device and install. If it asks for any
files, they will be in the "USB_DRIVERS"
folder on the cd.
:95, 98: Auto detects, and asks
for the files to install. Select the
files from the "USB_DRIVERS"
folder on the cd. |
|
|
|
3 |
|
Go
to Control Panel -> System ->
Hardware -> Device Manager ->
Ports and look for "Cypress USB-HID
-> COM device". If it is not
there, look for the group Human Interface
Devices -> USB Human Interface Device.
If it is there, skip to 5. |
|
|
|
|
|
Click
on update driver for "USB Human
Interface Device".
|
4b |
Select
"Install from a list or specific
location".
|
4c |
Select
"Don't search. I will choose the
driver to install."
|
4d |
Click
on "Have Disk", then "Browse".
In the browse box, go to the cd drive
that
the install cd is in, open "USB_DRIVERS"
folder, and select the file "HIDCOM.INF".
Click Open, then click OK.
|
4e |
"Cypress
USB-HID -> COM device" should
show up as a model option. Highlight
it, and click next.
|
4f |
A
popup may come up saying that the driver
"has not passed Windows Logo testing
to verify its compatibility with Windows
XP." and a bunch of other doom
and gloom. Click "Continue Anyway."
. |
4g |
The
drivers will install. |
|
|
|
5 |
|
Open
the "Ports (COM & LPT)"
group in the device manager and select
properties for "Cypress USB-HID
-> COM device". Set the port
speed to 9600. |
|
|
6 |
Set
the optical port speed in the Nexus®
meter to be 9600. (SC-6 SmartCoupler
doesn't support any other speed) |
|
|
7 |
Connect
to the Nexus® meter with the optical
port to verify the connection. |
|
|
|
|
I
am setting up the MV-90 TIM for the Nexus®
meter and I need to know the weight of the
pulse?
MV90
requires that the pulse weight be set to
one 1, but remember along with the pulse
weight you need a correct multiplier for
a correct read.
Here is an example:
CT 200:5 or 40:1
PT 7200:120 or 60:1
40 x 60 =2400
2400 x unit pulse weight (1) = 2400
MV-90 requires the multiplier to be divided
by 1000 before entering it MV-90 therefore
2400 / 1 = 2.4 multiplier that also must
be entered in MV-90
So in conclusion the pulse weight is 1 and
if the multiplier is not entered properly
the value measured will not be right. In
the example above the multiplier is 2.4.
What
is the CPU-1000?
The CPU-1000 is the component of the Futura+
that you connect the monitored voltages
and currents to. It is the 'black box' where
all the analog to digital conversion and
digital signal processing, and data logging
takes place. It houses any optional memory
and event inputs and relay output circuitry.
In addition to the CPU-1000, a typical installation
adds one or more display modules.
What display options
are available for the CPU-1000?
There are many available displays for the
Futura+. They range from a single row of
LEDs to three rows with multiple additional
enunciators.
P-11 - This is a single function
display, available for any measured value.
P14
- This display shows real power (Watts),
Total kilowatt hour (WH) and watt demand
(WD).
P15
- This display shows VAR / VARH / VARD with
6 digits of resolution.
P31
- Amps module displaying phases A-B-C and
N. Also displays %THD for each reading.
P32
- Volts module displaying A-N, B-N, C-N
phases, THD and K-Factor. Can also display
phase-to-phase readings.
P33
- Power module displays KW, KVAR, VA and
PF. The lower sector can be turned off for
a dual Watt / VAR display.
P34
- Multifunctional digital display with a
simultaneous 3-phase presentation of voltage,
current and power. It also displays %THD
and K-Factor for each voltage and current
reading.
How
many displays can I connect to the Futura+?
The
Futura+ can directly power up to four display
modules from the internal power supply of
the unit. Many more displays can be driven
if an external power supply, such as our
Power Brick PB1-9VO available with voltage
input range of 12 to 60 VAC/DC (D) or 90
to 240 VAC/DC (D2), is used to supply power
to the displays.
If
the display or cable to the display is running
outdoors for more than two hundred feet
an opto-isolator such as EIGs ISO485
is recommended. This isolates the meter
base from the displays and avoid grounding
loops for long display runs. Note the Nexus®
1250 meters have this function built-in.
Thus, this is only required for a Futura+.
View
the .PDF
file to get a wiring diagram
How
do I communicate with my PDA1000, CPU1000
or DM Series Meter Using Futura+ Communicator?
It
is a common complaint that people, when
using Futura+ Communicator, do not know
how to connect to the unit with the software.
The most common scenario is:
| DirectCom1:9600:0001 |
No
Device |
Status
??? |
This
usually means that the setting for signing
on or the meter setting are not configured
properly.
Below
is the information needed to communicate
with any of the devices.
- Baud
Rate (Ships from factory as 9600)
- Address
(Ships from factory as 0001)
- Protocol
(Ships from factory as EI)
- Cable
(Straight through NOT a cross over cable/null
mode
- Computers
Com Port (all computers are different
typically 1 sometimes 2 or 3)
Typical
Reasons Communication Cannot be Established
- User
changes factory defaults (Address, Baud
Rate, Protocol) and forgets what they
changed them too.
- Cable
is bad or user is using a cross over cable
(null modem)
- User
has computer on wrong Com Port. To check
your COM ports, go to Control Panel/System/Device
Manager/Ports (com & LPT)
Suggestions
to Try:
- Check
the Futura+ Communicator Setting
- Check
the Meters setting through the faceplate
- Check
your serial cable. People using a null
modem cable is the single biggest customer
support issue.
Note:
It is highly unlikely that the meter is
defective. Often, after trying these suggestions,
EI customer support can usually get it working
with you over the telephone.
Modem Communication Note:
If
you are using these metering devices with
an external modem, there are many additional
configuration issues that need to be addressed.
Since this is a daunting task, EIG designs
a Modem Manager product that is an RS485
to RS232 converter with built in functionality
so that you do not need to program the modem.
You can purchase this product at the factory.
We can rush one out to you ASAP to solve
any modem programming issues. It has been
our experience that the Modem Manager will
solve almost 100% of the modem communication
problems in the field. This will also work
with ANY RS485 device and will solve the
problems in the field. This has been a savior
for many of our customers (even with competitors
products).
Nexus®
meter users dont experience these
problems with the Nexus® meter's internal
modem because we built Modem manager right
into the Nexus® meter.
How
do I program the DMMS350 with my desired
IP address?
-
Connect the DMMS350 Ethernet port directly
to a computer with a crossover
cable or through a hub with a straight
Ethernet cable.
-
When running more recent versions of Windows
you should be verified that a
network connection has been established.
The link light (LK) on the DMMS350
should also light up when the connection
has been established.
-
Open the dos command window from Start
Menu -> Run… -> cmd
- Type
“arp –a” if table contains
an IP address skip step 5.
-
If empty arp table type “arp –s
0.0.0.0 00-00-00-00-00-00” to create
a generic arp
entry. Type “arp –a”
again and verify you now have a internet
address.

- Assign
your desired IP address by typing “arp
–s (desired IP address) (mac
address). In example below IP address
is 135.15.173.39, mac address 00-20-4a-
74-52-15. DO NOT FORGET THE SPACE BETWEEN
IP AND MAC
ADDRESS

- Type
“telnet 135.15.173.39 1” It
should fail in under 5 seconds. (substitute
your
IP address)
-
Type “telnet 135.15.173.39 9999”
-
You have now programmed your DMMS350 Ethernet
card. You can exit the
telnet screen.
How
do I get my DMMS+ to read a lower current
or voltage?
Refer to the meters instruction manual to
get in the programming mode. Once in the
programming mode follow the steps outlined
below.
Go to E by pressing the max/min/ limits
button
Press volts until a 5 is displayed
Press
Amps once, you should see E0 on top and
a value such as 0255 on the bottom.
Press
min/max/limits until you see E7 on the top
than press Amps.
A
value should be displayed in the center.
This value will vary depending on when you
purchased the meter. One of three different
values will appear (0044, 0075 or 0099).
The first number indicates the threshold
for voltage and the second number is for
the current. Let's use 0075 as an example.
The 7 is a number when doubled equals 14
this would be the approximate lowest threshold
voltage the meter can read. The 5 is a number
when doubled equals 10 which represents
the approximate lowest current the meter
can read. To change the threshold for current
you will only need to adjust the 5 and not
the 7. If are adjusting the voltage you
need only to adjust the 7 and not the 5.
To
adjust one of the two numbers press volts
until the desired number appears at the
bottom of the display then press amps to
save that digit. Press volts again to select
the desired second digit than press amps
again. The new value should be displayed
at the bottom of the screen now. I would
suggest lowering it in steps, one digit
at a time. CAUTION: Do not bring these numbers
down to zero or too low the meter will pick
up too much noise.
To exit press min/max/limits until EE is
displayed on top press amps twice and try
it. If further support is needed contact
customer support at 516-334-0870
or e-mail at support@electroind.com.
How
do I trouble shoot wiring errors with the
DMMS 300+?
The
DMMS 300+ is capable of troubleshooting
wiring mistakes. If the meter is in Delta
mode you will need to program it, temporarily,
to WYE. If you have negative power readings,
low power factor, large amount of neutral
current, you can use certain functions of
the DMMS 300+ to determine the cause of
the problem.
Trouble Shooting Negative Power Readings:
While in WYE mode press the "Power"
key and most of the light under the "Power"
label should light up. Press the "Phase/Next"
until the LED for "kW" or "MW"
lights up. Now press the "Power"
keys and do not release it. You should be
able to observe at that instant the total
power for each phase. You should see the
individual lights under the "AMPS"
label light up and a value of "kW"
or "MW" displayed on the bottom
display. If one of the is negative, that
would indicate that you have a reversed
wire on one of your "CT's". However
before you change the wiring on your CT
please review the following instructions.
Phase Reversal Detection
If your phase current A and your phase voltage
A are not on terminal 8,9 for current and
terminal 5 for voltage, the meter might
be flashing an alarm to indicate that it
is so. Pressing the " Max/Min/Limits"
key until the Limit light that is flashing
is lit and immediately after press the "Phase/Next"
key will indicate whether or not you have
some kind of phase reversal. In addition,
you can do the same test on power factor
and see if you have at least 0.7 power Factor
or above on all the phases. If you notice
a reading of for example: A= 0.9 B=0.5 C=0.2
you should try reversing B and C phase voltage.
You should see a positive change in your
power factor readings. You then check your
individual power for each Phase and swap
the current wires if you see a negative
power reading. The Rule here is to check
voltage wiring first then current.
What
are some programming tips for the DMMS 300+
equipped with Analog output modules?
Upon
receiving your meter already mounted with
an Analog Output module, you might want
to change the programming if the factory
default is not to your liking or reset it
to factory settings. For wiring diagrams
and others programming questions please
go to this URL address http://www.electroind.com/pdf/DCAnalog.pdf
. You will also need the DMMS 300+ installation
and operations manual to enter the programming
mode. Use this URL address to retrieve the
manual http://www.electroind.com/pdf/DMMS300350Manualrev4.8.pdf.
Follow the instructions provided by the
installation and operations manual to get
into the programming mode. The page to go
to is page 41 of the installation and operations
manual. Upon entering the programming mode
you should see the number "0."
Press the Max/Min/Limit key until you get
to "8." Press the "Amps"
key you should then see "8P.0"
appear at the top of the DMMS 300+ display
and four vertical bars on the bottom of
the display.
Factory Defaulted Analog Output Modules
The 6 and 10 Channel Analog output modules
store their calibration information on a
memory chip that is located on the analog
output module itself. These Analog output
modules are SEFI-1, SEFI-20, SHNI-1, and
SHNI-20. To retrieve the calibration information
from these outputs to your meter press the
"Amps" key while at "8P.0"
and you should see the vertical bars at
the bottom of the display move up to the
mid-section of the display. Once you reposition
the bars on the bottom of the display to
look the same as the middle of the display,
press the "Amps " key, the information
on the module is now transferred into the
meter. Note: the 2 and 4 channel modules
do not have factory storage capability.
A Simple Way To Get Your 6 Or 10 Channel
Module Up And Running When You Programmed
It Wrong
For example, if you have a unit that is
in saturation or showing a large amount
of current (i.e. 2 milliamps (for a 0-1mA)
or 23 milli amps (for a 4-20mA), and you
have another unit with a module that is
working.) You can retrieve the default calibration
information from a working module using
the above step. Without exiting the program,
remove the good analog output without disconnecting
the control voltage to the meter, and attach
the output that is saturating. Exit out
of the program while the saturating unit
is attached to the DMMS 300+. This automatically
stores the good data from meter to the saturating
module. Therefore the calibration data will
now be back in the saturated module and
will start working properly as long as the
voltage range of the two meters are the
same, if not see below.
The Importance 8P.0 In The Programming Mode
The position of the vertical bars on the
bottom of the display lets the DMMS 300+
meter know the type of output that is attached
to it and also indicates to the analog output
the voltage range of meter that is present.
Example: 150volts L-N, 300volts L-N, 75
volts L-N. The analog output will output
differently depending on the DMMS300+ voltage
range. For example 0 to 150 volts L-N =
0 to 20mA or 0 to 1mA. This is important
to note because if the saturated module
was calibrated for a different voltage range
unit, the above procedure will not work.
You will need to adjust the first two vertical
bars from left to right for the appropriate
voltage range.
| 75
volts L-N |
up
- down |
| 150volts
L-N |
down
- down |
| 300volts
L-N |
down
- up |
Is
there a quick reference guide to get into
DMVA 100 to change the PT and CT ratios?
The
DMVA 100 is password protected. To enter
the programming mode, key in the following
password. The password is 555.
NOTE:
THE METER WILL NOT STORE ANY PROGRAMMING
UNLESS PROPERLY EXITED.
ENTERING
THE PROGRAMMING MODE:
Step
1:
a. Press PRINT/PROG
until 3 appears in lower display.
b. Press PHASE/NEXT
to select.
c. 333
appear in lower display.
Step
2:
a. Digits begin scrolling
in upper display. The password is
555.
b. Press PHASE/NEXT
each time 5 appears.
c. The selected digits
appear in lower display.
d. Display blanks and
PPP flashes in upper display, confirming
a correctly entered password.
e. PPP
is replaced by 0. The meter
is now in the Programming Mode, GROUP 0.
GROUPS,
Functions, and Switch PACKS:
-
GROUPS are the main category.
-
Functions are sub categories of GROUPS.
-
Switch PACKS are sub categories of Functions.
| BUTTON |
FUNCTION |
DESCRIPTION |
|
| MAX/MIN/LIMITS |
ADVANCE |
Scrolls
groups, functions, and advances to exit
point from function and group level. |
| PRINT/PROG
|
CHANGE
VALUE |
Scrolls
packs, digit counters, and changes Switch
PACK position UP or DOWN. |
| VOLTS |
STORE |
Activates
new data entry, stores digits, and enters
or exits from group or function level. |
| FUNCTION
NUMBER |
FUNCTION |
0 |
Full
Scale Selection for Volts |
1 |
Full
Scale Selection for Amps |
E |
Exit
Programming GROUP 1 |
To
change the VOLT OR AMP FULL SCALE
settings (Function 0 and 1, respectively),
follow these steps:
NOTE: PRESS MAX/MIN/LIMITS,
AT ANY TIME, TO CANCEL BEFORE STORING THE
LAST DIGIT OR SWITCH.
Step
1:
a. Enter Group Level of
Programming Mode,
b. Press MAX/MIN/LIMITS
until 1. appears in upper display.
c. Press VOLTS
to activate the Group.
Step
2:
a. 10. appears in upper
display.
b. Lower display indicates
Full Scale setting.
c. A segment appears in
upper display.
d. UP signifies - Kilovolts.
e. DOWN signifies - Volts.
f Press VOLTS to begin Data Entry Sequence.
ENTERING
THE FULL SCALE FACTOR
Step
3:
A dash appears in lower display.
a. Press PRINT/PROG to
move the segment UP or DOWN.
b. Press VOLTS to store.
DECIMAL
POINT SELECTION
Step
4:
a. Press PRINT/PROG
to begin decimal placement.
b. Press VOLTS
to store
Step
5 :
Three dashes appear in lower display.
a. Press PRINT/PROG
for desired number.
· Press PRINT/PROG
once and the blank signifies a zero.
· Press PRINT/PROG
twice and 1 appears.
b. Press VOLTS
to store.
· repeat this procedure until desired
value is entered
· when complete, lower display indicates
new Full Scale setting.
Is
there a quick flow chart for the DM Series
Meters?
Yes.
This should make the programming easier.
Download
here.
How
do I interpet DNP data?
Understanding
the DNP values from DMMS 425 (DMMS300+)
meters.
The
following explains how to interpret DNP
raw data to match the readings on display.
This will be explained with more detailed
examples in this document. Refer DNP manual
(DNP3.0forFutura_DMRev.1.14.pdf)
for more information.
The
followings are the values returned from
DMMS425 by Class 0 poll.
Example
1:
Points 1,2,3 and 19 are current readings.
Appendices from the DNP manual explains
well how to interpret these readings. For
the point 0, use the equations to find out
the secondary value.
Secondary
value = (Analog Input/32768) * Secondary
Scale
= (212 / 32768) * 10 = 0.064697265625.
Now
multiply this number with CT ratio. The
ratio numerator is from point 15 and ratio
denominator is from point 16. Therefore,
The
Primary reading = 0.064697265625 * (2000/5)
= 25.87890625.
The
value 26A is on the Display for Phase A
current.
Example
2:
Points 4,5,6 are phase-to-neutral voltage
readings. Points 29-31 are phase-to-phase
voltage readings. For point 4, use the equation.
Secondary
value = (25710 / 32768) * 150 = 117.6910400390625.
Now
multiply this number with PT ratio. The
ratio numerator is from point 17 and ratio
denominator is from point 18. Therefore,
The
Primary reading = 117.6910400390625 * (120
/ 120) = 117.6910400390625.
The
value 117.7V is on the Display for Phase
AN voltage.
Example
3:
Points 7-14, 21-24 are power readings. Use
the equation for secondary reading for point
7.
Secondary
value = (109 / 32768) * 4500 = 14.9688720703125.
Now
multiply this number with CT, PT ratio.
The
Primary Reading = 14.9688720703125 * ( 2000
/ 5) * (120 / 120) = 5987.548828125.
The
Watt is 5987.6 W. The meter is showing 0.006
MW. This is acceptable.
Example
4:
The point 20 is frequency. The unit is centi-Hertz.
The
displayed reading = 5999 / 100 = 59.99 Hz
Example
5:
Points 25-29 are power factors. The unit
is 0.001.
For the point 25, the displayed reading
is 1.000.
How
do I set up my Modem Manager?
-
Turn the Modem Manager's RS485 BAUD dial
to reflect the RS485-bus baud rate.
-
Turn the Modem Manager's RS232 BAUD dial
to MODEM.
-
Slide the Modem Manager's DCE/DTE switch
to DTE.
-
Slide the Modem Manager's Half Duplex/Full
Duplex switch to Half Duplex for a 2-wire
RS485 bus or Full Duplex for a 4-wire
RS485 bus.
-
Plug the Modem Manager's 9V AC/DC plug
into an outlet.
-
Connect the phone line to the modem.
-
Connect the modem to the Modem Manager
with a serial cable.
-
Connect the Modem Manager to the RS485
bus. (See the manual appendices for diagrams
of a typical RS485-bus connection.) -
Turn the modem on and then turn the Modem
Manager on.
Why
do I lose communication with my modem when
I am retrieving information over the telephone
line from a device? What can I do to solve
this problem?
Modems
are designed to operate with computers and
require several control lines to function
properly. Because these control lines are
not available on an RS485 bus, modems are
less suitable for and more difficult to
use in remote applications.
Typical phone lines are voice grade and
the quality of the connection can vary from
location to location. Modems are designed
to communicate with each other by negotiating
a baud rate that provides the most reliable
data transfers. This can range from 300
to 57.6 baud.
However,
the baud rate of an RS485 bus is fixed,
thus limiting the modems to communicating
at this fixed rate. If this rate cannot
be negotiated, the connection cannot be
established.
Another
problem is line dropouts. Even if the communication
rate is established, noise can cause intermittent
line dropouts. Since there are no control
lines on an RS485 bus, there is no way to
stop the flow of data to the modem. In many
cases, the modem buffer fills and overruns,
causing loss of data, communication errors,
and in many cases, loss of the actual connection.
There is also the issue of determining how
the remote modem will answer, and after
how many rings.
Modem
Manager solves all of these problems. It
contains all the lines necessary to control
the modem. Its large buffer and independent
communication ports permit modems to negotiate
optimum communication rates while allowing
fixed RS485 bus rates. It initializes the
modem, it answers the phone when a call
is received and it controls the flow of
data to the modem during dropouts. This
eliminates most common problems.
This
device improves all forms of communication,
from noisy phone lines to cellular communications
and radio transmissions. While no communication
is in progress, the MM1 periodically resets
the modem (every five to ten minutes) to
clear any glitches or hang-ups due to power
dropouts.
What
are the polarization requirements to use
DC to power the Unicom 2500?
The
Unicom 2500 is designed to operate on 9
to 24 Volts, either DC or AC. Its design
allows any polarity of plug to be used with
either AC or DC.
What
product do I buy to replace my Old VA, LM
or LF series meters?
Due
to the inability to obtain parts for our
legacy products, EI had discontinued our
LM,VA and LF series meters. If you need
to upgrade or replace the unit, your correct
product will be the following:
For
50/60Hz systems, you will need the DMVA100F
Download:
DMVA100F Brochure
For higher frequencies, you will need the
F Series Single function meters.
Download:
F Series Data Sheet
DM
and F Series Dimensional Differences:
Download
Retrofit Dimensions
|